Give suppliers a decision-ready starting point.
A useful project brief states the operating objective, known constraints and decisions still open. You do not need a finished design to start a discussion, but a target capacity without a load profile or connection boundary rarely supports a dependable equipment proposal.
Use a one-page brief with supporting files.
| Field | Useful entry | Avoid |
|---|---|---|
| Objective | Reduce a measured evening import peak | We need a battery |
| Demand | Interval data with units, dates and meter location | A monthly bill presented as a peak-load profile |
| Connection | Available capacity, voltage, frequency and single-line diagram | Assuming transformer nameplate equals spare site capacity |
| Site | Location, space, access and environmental conditions | Country name only |
| Programme | Required operating date and procurement milestones | An unqualified urgent deadline |
| Open decisions | Export limit and backup scope awaiting confirmation | Leaving unknowns blank |
Example: turn a request into an engineering question.
Initial request: “Quote a 261 kWh cabinet.” Better brief: “Our illustrative factory imports 180 kW for 90 minutes after production ramps up. We want to assess a 120 kW import ceiling. Please evaluate a 60 kW discharge duty and at least 90 kWh delivered to the load, with usable capacity, losses and reserve stated separately.”
The example defines a duty, not a final product. Include recharge opportunities, seasonal variation and the frequency of the event. Backup, if required, needs its own critical-load list and transfer-performance requirements.
Attach the right evidence.
Provide the current single-line diagram, equipment list, interval energy data, layout and relevant utility correspondence. Label each file with a date and revision. For a retrofit, identify existing inverter, transformer, protection and control equipment. For a new build, distinguish approved requirements from preliminary assumptions.
Make the next deliverable explicit.
| Stage | Expected output |
|---|---|
| Initial review | Missing-information list and proposed equipment boundary |
| Technical alignment | Selected configuration, interface questions and deviations |
| Commercial proposal | Priced scope, exclusions, programme and service responsibilities |
| Order readiness | Agreed documents, tests and change-control process |
Send the brief through our contact page. WAYTON can help organize equipment options and supplier responses around the stated requirement.